Footings & Dirt

As regular readers know, I’m not a firm believer in the use of precast concrete cookies for footing pads for many reasons.

(for further spirited reading on this very subject: https://www.hansenpolebuildings.com/blog/2012/08/hurl-yourconcrete-cookies/)

Pole Building Footings and Frost DepthIt turns out there are “some” pole building providers who make cookies work on paper, by using an assumed presumptive load-bearing value for the soil of 3000 psf (pounds per square foot).

Chapter of the 2012 IBC (International Building Code) deals with the specifics of Soils and Foundations. With Section 1806 dedicated to Presumptive Load-Bearing Values of Soils.

From IBC 1806.1 Load combinations.

The presumptive load-bearing values provided in Table 1806.2 shall be used with the allowable stress design load combinations specified in Section 1605.3. The values of vertical foundation pressure and lateral bearing pressure given in Table 1806.2 shall be permitted to be increased by one-third where used with the alternative load combinations of Section 1605.3 that include wind or earthquake loads.

At least in the case of pole buildings designed by the Hansen Pole Buildings engineers, the alternative load combinations are used, so the one-third increase is allowable.

IBC 1806.2 Presumptive load-bearing values.

The load-bearing values used in design for supporting soils near the surface shall not exceed the values specified in Table 1806.2 unless data to substantiate the use of higher values are submitted and approved. Where the building official has reason to doubt the classification, strength or compressibility of the soil, the requirements of Section 1803.5.2 shall be satisfied. 

      I bring you, for your reading enjoyment 1803.5:

“Where the classification, strength or compressibility of the soil is in doubt or where a load-bearing value superior to that specified in this code is claimed, the building official shall be permitted to require that a geotechnical investigation be conducted.”

Returning to our regularly scheduled programming:  

Presumptive load-bearing values shall apply to materials with similar physical characteristics and dispositions. Mud, organic silt, organic clays, peat or unprepared fill shall not be assumed to have a presumptive load-bearing capacity unless data to substantiate the use of such a value are submitted. 

Exception: A presumptive load-bearing capacity shall be permitted to be used where the building official deems the load-bearing capacity of mud, organic silt or unprepared fill is adequate for the support of lightweight or temporary structures.

So, if the Building Official doesn’t believe the numbers being assumed, he can require (not request) the hiring of a soils engineer to validate the soil strength.

TABLE 1806.2 PRESUMPTIVE LOAD-BEARING VALUES 

CLASS OF MATERIALS VERTICAL FOUNDATION PRESSURE (psf) LATERAL BEARING PRESSURE
(psf/ft below natural grade)
LATERAL SLIDING RESISTANCE
Coefficient of frictiona Cohesion (psf)b
1. Crystalline bedrock 12,000 1,200 0.70
2. Sedimentary and foliated rock 4,000 400 0.35
3. Sandy gravel and/or gravel (GW and GP) 3,000 200 0.35
4. Sand, silty sand, clayey sand, silty gravel and clayey gravel (SW, SP, SM, SC, GM and GC) 2,000 150 0.25
5. Clay, sandy clay, silty clay, clayey silt, silt and sandy silt (CL, ML, MH and CH) 1,500 100 130

 

While GW and GP type soils do exist, they most certainly do not predominate. In most instances, 2000 or even 1500 psf soils are much more likely to be the case.

The entire goal is to end up with footings beneath columns which are adequately sized in diameter so the building will not settle under its own weight plus the design snow (or roof) load.

Think of soil strength as being directly the inverse of how easy it is to dig a hole. If it digs easy – the footings are going to be larger in size. If in doubt, play it safe, a few extra yards of pre-mix concrete to increase the diameter of footings, is a small price to pay!

4 thoughts on “Footings & Dirt

  1. I need help on the chart 1806.2a amended how do you calculate a footing size for lose gravel for 72,000 kips/pounds the chart says 2 tons per square foot the answer is 6 ‘6” squared how do you calculate this

    Reply
    1. A 72,000# load on a footing is a large load! Please keep in mind, my advise is not to take precedence over or replace information provided by a Registered Professional Engineer (whom I would recommend you consult with).

      You loose gravel is presumably a Class 4 material (silty gravel), able to support 2000 psf (one ton, not two). A geotechnical engineer could be engaged to do site specific testing, Usually tested values come in higher than presumptive values and could reduce your footing size.

      72,000# / 2000psf = 36 square feet of footing (or 6′ x 6′).

      Reply
  2. Is that 72,000# on one footing or total load of structure spread over several footings. Makes big difference.

    Reply
    1. Not sure where you are seeing the 72,000#? For single story a 72,000# building would be somewhere around 9000 square feet and the load would be distributed probably 40 footings.

      Reply