Tag Archives: ceiling vapor barrier

Condensation Control, Ventilation or Insulation

Most Builders Do Not Understand Condensation Control, Ventilation or Insulation

Crucial to proper performance of climate controlled buildings of any sort is condensation control, adequate ventilation and insulation. Sadly, most builders do not understand how to come up with a proper design solution.

Reader AARON in WISCONSIN DELLS writes:

“Hello, I was wondering if you had a minute for a quick question ? I have read posts for countless hours regarding vapor barrier between trusses and roof steel and I can’t find the answer I’m looking for. I’m building a 44×96 that will have in floor heat in South central Wisconsin (by Madison) so we have cold winters and humid summers. Walls will be spray foamed. I will be applying a vapor barrier (poly) to the bottom of roof trusses and then putting a metal ceiling on and spraying fiberglass insulation above the ceiling. Fully vented ridge cap and 2’ overhangs with vented soffits around the entire building. The builder did not put any vapor barrier down between the roof steel and the trusses so the steel is directly on the trusses. Could this end up creating a moisture issue or will I have enough air flow in the attic space that I do not need the vapor barrier between the roof metal and trusses ? Thank you very much for your time.”

Thank you for reaching out to me Aaron, I am always available to answer questions.

Your builder sadly did you no favors in not having a means to prevent condensation on your roof steel underside. It also requires having an actual thermal break, not just a vapor barrier. Your best solution now is to have two inches of closed cell spray foam applied directly to the underside of your roof steel, making certain they do not block ridge vents. Without this thermal break, expect to end up with damp insulation.

If your builder installed vented soffits on your building’s end overhangs, you need to find a method to block them off – otherwise your attic will not vent properly.

In regards to ceiling vapor barriers, Joe Lstiburek (building scientist and founding principal of Building Science Corporation) says plastic vapor barriers should only be installed in vented attics in climates with more than 8,000 heating degree days. Even in South central Wisconsin, you are not to this point.

You’ll want to verify a correct ratio of air intake from soffits to air exhaust at ridge (chances are good your builder did not). At least 40% and no more than 50% of your attic’s net free ventilating area (NFVA) should be at the ridge. You may need to block off some of your sidewall eave vents to get the ratio correct.

I would also recommend you blow in rockwool insulation in your attic rather than fiberglass. Fiberglass insulation loses R value when outside (attic) air temperatures are low and is also affected by even small amounts of moisture.

Does My Pole Barn Need a Vapor Barrier?

Does My Pole Barn Need a Vapor Barrier Above the Metal Ceiling?

Reader DAVID in BALDWINSVILLE writes:

“I have a new pole barn with bubble vapor barrier under roof metal. I am installing a metal ceiling with R-38 cellulose in the attic. Do I need a vapor barrier above the metal ceiling? The barn will be heated somewhat in winter.”

From Mike the Pole Barn Guru:

Kudos to you for recognizing bubble wrap products advertised as ‘insulation’ are, at best, a good vapor barrier if properly sealed!

My son Brent is working on his doctorate at UMass Amherst, so I utilized Building and Construction Technology information from their Department of Environmental Conservation in penning this response.

My concern is with blowing in cellulose above a steel ceiling. From UMass:

“Wet insulation of any stripe is bad. But cellulose is hygroscopic. It’s able to soak and hold liquid water. Undetected leaks can wet cellulose causing it to sag within framing cavities. Water leaks can compress the blanket of fiber and in extreme cases, can create a void space, degrading its thermal value. Another concern is that chemicals used to protect cellulose from fire make it potentially corrosive in wet environments. Tests conducted by the Oak Ridge National Laboratory show chemical treatments used to treat cellulose can cause metal fasteners, plumbing pipes and electrical wires to corrode if left in contact with wet, treated cellulose insulation for extended periods of time. “

I’d much prefer to see you blowing in rockwool as it remains unaffected by moisture. Last thing you want is to have damp cellulose insulation chemicals eating holes in your ceiling.

According to building scientist and founding principal of Building Science Corporation Joe Lstiburek, “Plastic vapor barriers should only be installed in vented attics in climates with more than 8,000 heating degree days.”

As your site has under 8000 heating degree days a year, you should not have a ceiling vapor barrier. You do need to ensure your newly created non-conditioned dead attic space is adequately ventilated at eave and ridge (https://www.hansenpolebuildings.com/2018/03/adequate-eave-ridge-ventilation/).

For extended reading on heating degree days, please see: https://www.hansenpolebuildings.com/2022/11/what-is-degree-day/

Cellulose for a Pole Barn Attic

Multiple options are available for insulating attics of post frame (pole barn) attics. Reader NATE in BURNHAM writes:

“Hello! I have been doing some research all evening and I can’t seem to find an answer. I did take the time to read some various forums and blogs regarding this subject to no avail…having said that, here is my question; According to the attached spec sheet for my roof trusses (4ft O.C) spanning my 52Lx28Wx10H pole building, would blown in cellulose insulation at an R38 value combined with 6ml plastic sheeting (vapor barrier) and thin gauge metal ceiling be supported? I do know from the specs that my BCDL is 5psf. Any help on this would be wonderful as I am at a stopping point in finishing my garage. Thank you!”

Mike the Pole Barn Guru advises:

I am going to hopefully change some of your plans here….

Unless your building is where there are 8000 heating degree days or more, you should not have a ceiling vapor barrier (no 6ml plastic sheeting). In Pennsylvania you are well under this requirement (Northern Minnesota would qualify). You do need to have sufficient eave intake and ridge exhaust ventilation to allow warm moist air from inside of your building to be vented out above your insulation. Your total NFVA (Net Free Ventilation Area) must be no less than 699 square inches, with at least 50% and no more than 60% located at the sidewall eaves.

Blown in cellulose weighs roughly 2.5 to 3 pcf (pounds per cubic foot). Blown in cellulose will settle as much as 20% and can take up to two years to do so. Cellulose gives R-3.5 per inch, so your R-38 would be 10.86 inches thick (after settle), so I would plan on no less than 13.5 inches blown in to achieve your R-38. To be safe, I would assume 3.4 psf (pounds per square foot). Besides settling, blown cellulose does have another downside – in order to be fire retardant it is treated with borax or boric acid. Borates can be corrosive to steel in humid or moist environments, so you may want to consider a different insulation type, such as fiberglass. Fiberglass is also lighter weight, coming in at about a pound per cubic foot.

Steel liner panels are most typically 29 gauge steel weighing in around 0.6 psf.

Your five psf BCDL (bottom chord dead load) has to also account, in part, for weight of your trusses and bottom chord bracing, as well as any electrical and light fixtures. Most often this is considered to be a pound per square foot. This is going to put your proposed use of cellulose right at capacity, without any remaining margin for error.